After a disturbance, everyone from the plant to the Reliability Coordinator needs to know what the IBR actually did. Too often the data wasn't there. PRC-028-1 closes that gap by requiring high-resolution, time-synchronized recording at inverter-based resources.
What it requires
- SER for breaker and status changes (R1)
- Fault recording, with at least 2 cycles of pre-trigger data and at least 2.0 seconds total (R2–R3)
- Continuous dynamic disturbance recording, sampling at 960 samples/s or more and storing 60 records/s or more (R4–R5)
- UTC time synchronization: ±1 ms for most recorders, ±100 ms for IBR unit data (R6)
- Data retrievable for 20 calendar days and provided within 15 days of a request; fault records as CSV or IEEE C37.111 COMTRADE (R7)
- Failed recording capability restored within 90 days, or a CAP submitted (R8)
Where teams struggle
Recording is spread across relays, DFRs, inverters and plant controllers. Coverage is validated by hand, legacy equipment is a question mark, and most organizations have no continuous way to know the data is being captured until they need it. By then it's too late.
What our check does
It's not a task tracker or a document store; it performs the check:
- Verifies SER, FR and DDR coverage against the required elements
- Checks record length, pre-trigger, sample rates and channel configuration
- Checks clock synchronization against the R6 tolerances
- Confirms retention and retrieval readiness
- Flags gaps early, while there's still time to fix them
PRC-028 data is also the input to PRC-029-1 and PRC-030-1. Checking it continuously is what makes the other two possible.