Relay device numbers (IEEE C37.2) in NERC PRC compliance
What 21, 24, 27, 40, 51V, 59, 81, 87 and the other device numbers mean, and which NERC standard checks each one: PRC-024-4, PRC-025-2, PRC-019-2 or PRC-005-6.
Written for protection and compliance engineers. Checked against NERC sources on November 12, 2026.
The short answer
IEEE C37.2 device numbers are the shorthand on every one-line and setting sheet: 21 is distance, 27 undervoltage, 59 overvoltage, 81 frequency, 24 volts-per-hertz, 51V voltage-restrained overcurrent, 40 loss of field, 87 differential. In NERC PRC work they tell you which standard applies to which element: 27, 59, 81 and 24 are checked under PRC-024-4; 21, 50/51, 51V and 67 under PRC-025-2; 40 and 24 against the limiters under PRC-019-2; and every protective relay in the trip path under PRC-005-6.
Device numbers in NERC PRC work
| No. | Device | What it does | Where it shows up in NERC compliance |
|---|---|---|---|
| 21 | Distance relay | Operates on impedance (voltage over current) inside a set reach | PRC-025-2 load-responsive relay; PRC-026 power swing evaluation |
| 24 | Volts per hertz relay | Operates when V/Hz exceeds a set value; protects generators and transformers from overexcitation | PRC-024-4 (in scope for the no-trip zone); PRC-019-2 against the V/Hz limiter |
| 25 | Synchronism-check relay | Permits closing only when both sides are within angle, slip and voltage limits | PRC-005 maintenance |
| 27 | Undervoltage relay | Operates below a set voltage | PRC-024-4 Attachment 2; IBR equivalents under PRC-029-1 |
| 32 | Directional power relay | Operates on power flow in a set direction, such as reverse power into a generator | PRC-005 maintenance |
| 40 | Field (loss-of-excitation) relay | Operates on loss or low level of generator field | PRC-019-2, coordinated with the underexcitation limiter (UEL) |
| 46 | Negative-sequence (phase-balance) current relay | Operates on current unbalance that heats the rotor | PRC-005 maintenance |
| 49 | Thermal relay | Operates on machine or transformer temperature | PRC-005 maintenance where it trips |
| 50 | Instantaneous overcurrent relay | Operates with no intentional delay above a set current | PRC-025-2 when load-responsive |
| 51 | AC time overcurrent relay | Operates after a delay that shortens as current rises | PRC-025-2 |
| 51V | Voltage-restrained or voltage-controlled overcurrent relay | Time overcurrent whose pickup depends on voltage (51V-R restrained, 51V-C controlled) | PRC-025-2 |
| 52 | AC circuit breaker | The breaker itself; its position is a status point | PRC-028-1 SER breaker position |
| 59 | Overvoltage relay | Operates above a set voltage (59N: neutral overvoltage, used for stator ground) | PRC-024-4 Attachment 2; IBR equivalents under PRC-029-1 |
| 64 | Ground detector relay | Detects ground faults (64G stator ground, 64F field ground) | PRC-005 maintenance |
| 67 | AC directional overcurrent relay | Overcurrent that operates only for current in a set direction | PRC-025-2 when load-responsive |
| 68 | Blocking relay (power swing blocking) | Blocks tripping during a power swing | PRC-026 power swing evaluation |
| 78 | Out-of-step (phase-angle measuring) relay | Trips on loss of synchronism | PRC-026 power swing evaluation |
| 79 | Reclosing relay | Recloses a breaker automatically after a trip | PRC-005-6 Automatic Reclosing |
| 81 | Frequency relay | Operates on frequency (81U under, 81O over, 81R rate of change) | PRC-024-4 Attachment 1; IBR equivalents under PRC-029-1 |
| 86 | Lockout relay | Trips and holds out until reset by hand | PRC-005-6 (auxiliary and lockout relays in the trip path) |
| 87 | Differential relay | Operates on the difference between currents in and out of a zone (87G generator, 87T transformer, 87B bus) | PRC-005-6 maintenance |
| 94 | Tripping relay | Trips a breaker on command from other relays | PRC-005-6 (in the trip path) |
Definitions are our plain-language summaries of IEEE C37.2 usage; the standard is authoritative. PRC-026 is listed for context; data phleet doesn't automate it today.
By standard
- PRC-024-4: 81U/81O against Attachment 1; 27 and 59 against Attachment 2 at the GSU high side; 24.
- PRC-025-2: 21, 50/51, 51V, 67 on the generator, GSU, unit auxiliary transformer and elements serving the unit.
- PRC-019-2: 40 vs UEL, 24 vs V/Hz limiter, overcurrent protection vs OEL and stator current limiter, all on the capability curve.
- PRC-005-6: every protective relay that responds to electrical quantities, plus 79 reclosing and sudden pressure relaying.
- PRC-028-1: 52 breaker position as SER data.
Where data phleet fits
data phleet reads the 27, 59, 81 and 24 elements, the load-responsive 21 and 51V elements and the rest straight out of relay settings files and setting sheets, places each one against the standard it belongs to, and flags what needs your engineers' review. See which file formats it reads.
Related questions
Which relay elements are in scope for PRC-024-4?
Frequency protection (81) under Attachment 1, and voltage protection (27, 59) under Attachment 2, plus volts-per-hertz (24), which is easy to forget. Voltage settings must be converted from the relay's measuring point to the high side of the GSU before comparing with the no-trip zone.
Which relays does PRC-025-2 cover?
Load-responsive protective relays at the terminals of the listed generation elements: typically phase distance (21), phase overcurrent (50/51), voltage-restrained or voltage-controlled overcurrent (51V) and directional overcurrent (67). Each must meet the Attachment 1 criteria for its application.
Which relays matter for PRC-019-2?
The protection that the voltage regulating limiters must operate ahead of: loss-of-field (40) against the underexcitation limiter, volts-per-hertz (24) against the V/Hz limiter, and field or stator overcurrent protection against the overexcitation and stator current limiters.
Do inverter-based resources use these device numbers?
Inverters have trip functions that act like 27, 59 and 81, but they're usually inverter settings rather than separate relays. Since October 1, 2026 their ride-through is governed by PRC-029-1, not PRC-024-4. Plant-level relays at the collector system and main power transformer still use C37.2 numbers.
What do suffixes like G, T, N and V mean?
They qualify the device: G generator (or ground), T transformer, N neutral, B bus, L line, V voltage (as in 51V), U and O for under and over (81U, 81O), R for rate (81R). Usage varies a little between utilities, so check your own drawing standards.