Relay device numbers (IEEE C37.2) in NERC PRC compliance

What 21, 24, 27, 40, 51V, 59, 81, 87 and the other device numbers mean, and which NERC standard checks each one: PRC-024-4, PRC-025-2, PRC-019-2 or PRC-005-6.

Written for protection and compliance engineers. Checked against NERC sources on November 12, 2026.

The short answer

IEEE C37.2 device numbers are the shorthand on every one-line and setting sheet: 21 is distance, 27 undervoltage, 59 overvoltage, 81 frequency, 24 volts-per-hertz, 51V voltage-restrained overcurrent, 40 loss of field, 87 differential. In NERC PRC work they tell you which standard applies to which element: 27, 59, 81 and 24 are checked under PRC-024-4; 21, 50/51, 51V and 67 under PRC-025-2; 40 and 24 against the limiters under PRC-019-2; and every protective relay in the trip path under PRC-005-6.

Device numbers in NERC PRC work

No.DeviceWhat it doesWhere it shows up in NERC compliance
21Distance relayOperates on impedance (voltage over current) inside a set reachPRC-025-2 load-responsive relay; PRC-026 power swing evaluation
24Volts per hertz relayOperates when V/Hz exceeds a set value; protects generators and transformers from overexcitationPRC-024-4 (in scope for the no-trip zone); PRC-019-2 against the V/Hz limiter
25Synchronism-check relayPermits closing only when both sides are within angle, slip and voltage limitsPRC-005 maintenance
27Undervoltage relayOperates below a set voltagePRC-024-4 Attachment 2; IBR equivalents under PRC-029-1
32Directional power relayOperates on power flow in a set direction, such as reverse power into a generatorPRC-005 maintenance
40Field (loss-of-excitation) relayOperates on loss or low level of generator fieldPRC-019-2, coordinated with the underexcitation limiter (UEL)
46Negative-sequence (phase-balance) current relayOperates on current unbalance that heats the rotorPRC-005 maintenance
49Thermal relayOperates on machine or transformer temperaturePRC-005 maintenance where it trips
50Instantaneous overcurrent relayOperates with no intentional delay above a set currentPRC-025-2 when load-responsive
51AC time overcurrent relayOperates after a delay that shortens as current risesPRC-025-2
51VVoltage-restrained or voltage-controlled overcurrent relayTime overcurrent whose pickup depends on voltage (51V-R restrained, 51V-C controlled)PRC-025-2
52AC circuit breakerThe breaker itself; its position is a status pointPRC-028-1 SER breaker position
59Overvoltage relayOperates above a set voltage (59N: neutral overvoltage, used for stator ground)PRC-024-4 Attachment 2; IBR equivalents under PRC-029-1
64Ground detector relayDetects ground faults (64G stator ground, 64F field ground)PRC-005 maintenance
67AC directional overcurrent relayOvercurrent that operates only for current in a set directionPRC-025-2 when load-responsive
68Blocking relay (power swing blocking)Blocks tripping during a power swingPRC-026 power swing evaluation
78Out-of-step (phase-angle measuring) relayTrips on loss of synchronismPRC-026 power swing evaluation
79Reclosing relayRecloses a breaker automatically after a tripPRC-005-6 Automatic Reclosing
81Frequency relayOperates on frequency (81U under, 81O over, 81R rate of change)PRC-024-4 Attachment 1; IBR equivalents under PRC-029-1
86Lockout relayTrips and holds out until reset by handPRC-005-6 (auxiliary and lockout relays in the trip path)
87Differential relayOperates on the difference between currents in and out of a zone (87G generator, 87T transformer, 87B bus)PRC-005-6 maintenance
94Tripping relayTrips a breaker on command from other relaysPRC-005-6 (in the trip path)

Definitions are our plain-language summaries of IEEE C37.2 usage; the standard is authoritative. PRC-026 is listed for context; data phleet doesn't automate it today.

By standard

  • PRC-024-4: 81U/81O against Attachment 1; 27 and 59 against Attachment 2 at the GSU high side; 24.
  • PRC-025-2: 21, 50/51, 51V, 67 on the generator, GSU, unit auxiliary transformer and elements serving the unit.
  • PRC-019-2: 40 vs UEL, 24 vs V/Hz limiter, overcurrent protection vs OEL and stator current limiter, all on the capability curve.
  • PRC-005-6: every protective relay that responds to electrical quantities, plus 79 reclosing and sudden pressure relaying.
  • PRC-028-1: 52 breaker position as SER data.

Where data phleet fits

data phleet reads the 27, 59, 81 and 24 elements, the load-responsive 21 and 51V elements and the rest straight out of relay settings files and setting sheets, places each one against the standard it belongs to, and flags what needs your engineers' review. See which file formats it reads.

Related questions

Which relay elements are in scope for PRC-024-4?

Frequency protection (81) under Attachment 1, and voltage protection (27, 59) under Attachment 2, plus volts-per-hertz (24), which is easy to forget. Voltage settings must be converted from the relay's measuring point to the high side of the GSU before comparing with the no-trip zone.

Which relays does PRC-025-2 cover?

Load-responsive protective relays at the terminals of the listed generation elements: typically phase distance (21), phase overcurrent (50/51), voltage-restrained or voltage-controlled overcurrent (51V) and directional overcurrent (67). Each must meet the Attachment 1 criteria for its application.

Which relays matter for PRC-019-2?

The protection that the voltage regulating limiters must operate ahead of: loss-of-field (40) against the underexcitation limiter, volts-per-hertz (24) against the V/Hz limiter, and field or stator overcurrent protection against the overexcitation and stator current limiters.

Do inverter-based resources use these device numbers?

Inverters have trip functions that act like 27, 59 and 81, but they're usually inverter settings rather than separate relays. Since October 1, 2026 their ride-through is governed by PRC-029-1, not PRC-024-4. Plant-level relays at the collector system and main power transformer still use C37.2 numbers.

What do suffixes like G, T, N and V mean?

They qualify the device: G generator (or ground), T transformer, N neutral, B bus, L line, V voltage (as in 51V), U and O for under and over (81U, 81O), R for rate (81R). Usage varies a little between utilities, so check your own drawing standards.