Reference · File formats

Relay settings and disturbance record file formats for NERC compliance

SEL .rdb, GE .urs, DIGSI, PCM600, Easergy Studio, IEC 61850 SCL and COMTRADE: what each file holds, which NERC standard uses it, and which ones data phleet reads directly.

Written for protection and compliance engineers. Checked against NERC sources on November 12, 2026.

The short answer

NERC PRC evidence starts in vendor files: SEL QuickSet .rdb databases, GE EnerVista .urs files, DIGSI, PCM600 and Easergy Studio projects, COMTRADE disturbance records and the setting sheets exported from all of them. data phleet reads SEL .rdb, COMTRADE (.cfg/.dat/.hdr and .cff), and settings reports, drawings and records in PDF, Excel, CSV, Word, Visio and images directly. For other relay platforms, send the exported settings report.

Formats, by source

SourceTool / formatFilesdata phleet
SEL (Schweitzer)AcSELerator QuickSet settings database.rdbReads natively. Settings by group and class, with relay metadata and version
Disturbance recorders, relays and invertersCOMTRADE (IEEE C37.111: 1991, 1999, 2013).cfg .dat .hdr, single-file .cffReads natively. Channels, scaling, CT and PT ratios, sample rates, UTC start time, waveforms
Setting sheets and reportsExported from any vendor toolPDF, Excel (.xlsx, .xlsm), CSV, Word (.docx)Reads natively. Element settings, pickups and delays from the document
DrawingsOne-lines, three-lines, network diagramsPDF, Visio (.vsdx), imagesReads natively. Devices, ratings and connections for the inventory and topology
GE Vernova (Multilin) UREnerVista UR Setup.ursSend the settings report exported from EnerVista (PDF, Excel or CSV). Ask us about native support
Siemens SIPROTECDIGSIDIGSI project and device filesSend the exported settings report. Ask us about native support
Hitachi Energy (ABB) RelionPCM600PCM600 project filesSend the exported settings report. Ask us about native support
Schneider Electric MiCOM / EasergyEasergy Studio (formerly MiCOM S1)Easergy Studio setting filesSend the exported settings report. Ask us about native support
IEC 61850 substationsSystem Configuration Language (SCL).icd .cid .scd .iidAsk us; configuration data, not protection settings, for most PRC checks
Other recordsSER logs, CMMS exports, rosters, structured dataCSV, Excel, JSONReads natively. Maintenance dates, events, personnel and access records

Native support as of November 2026. Vendor and tool names are their owners' trademarks.

What gets pulled out, and which standard uses it

  • Frequency, voltage and V/Hz elements (81, 27, 59, 24): pickups and delays for PRC-024-4.
  • Load-responsive elements (21, 50/51, 51V, 67): reach, pickup and curve for PRC-025-2.
  • Loss-of-field and limiter-related elements (40, 24): for coordination under PRC-019-2.
  • CT and PT ratios from settings and COMTRADE configuration: needed to convert relay quantities to primary values.
  • Recorder configuration and waveforms from COMTRADE: sample rates, record length and channels for PRC-028-1; real power over time for PRC-030-1 screening.

Device numbers explained: relay device numbers (IEEE C37.2).

Tips for audit-ready settings files

  • Keep the file the relay was actually loaded from, dated, not just a later export.
  • Record which settings group is active; multi-group relays are a common source of PRC-024 surprises.
  • Name COMTRADE files consistently (IEEE C37.232 helps) and keep them in UTC.
  • Store the settings file with the change record, so a re-run after the change has its input.

Related questions

Can data phleet read SEL .rdb files?

Yes. data phleet reads AcSELerator QuickSet .rdb settings databases directly, including settings by group and class and the relay's metadata, so 27, 59, 81, 24, 21 and 51 elements come straight from the file with no transcription.

What is the difference between COMTRADE .cfg, .dat and .cff files?

A COMTRADE record (IEEE C37.111) is a .cfg configuration file describing channels, scaling, sample rates and the start time, plus a .dat file of samples, with optional .hdr and .inf files. The 2013 revision added .cff, which holds all of them in one file. data phleet reads both forms.

Our relays aren't SEL. Can we still use data phleet?

Yes. Export the settings report from the vendor's tool (EnerVista, DIGSI, PCM600, Easergy Studio and so on) as PDF, Excel or CSV and data phleet reads the settings from it. If you have a large fleet on one platform, ask us about native file support.

How should COMTRADE files be named?

IEEE C37.232 (COMNAME) defines a naming convention that puts the date, time, station and device in the file name. It isn't required by NERC, but it makes PRC-028 and PRC-030 records far easier to find and match to events.

Send us one settings file.

SEL .rdb, a settings report or a COMTRADE record. We'll show you what comes out of it, live.