How to screen COMTRADE records for PRC-030-1 events
A step-by-step method for finding every unexpected IBR output reduction in your disturbance records, applying the exclusions, and keeping the screening log an auditor will ask for.
Checked against the NERC standard on November 12, 2026.
The short answer
To screen a COMTRADE record for PRC-030-1 R1, get the plant's real power output at high resolution, slide a 4-second window across the whole record, and flag any window where output falls by at least 20 MW and at least 10% of gross nameplate, or falls to zero. Then test each flagged event against the four exclusions using irradiance, wind, dispatch, breaker and PRC-004 records, and log the result for every record, qualifying or not. The log is your evidence that the R1 process runs.
Step by step
- Collect the records. The fault and dynamic disturbance recordings your PRC-028-1 recorders write (IEEE C37.111 COMTRADE: a .cfg file describing channels, sample rates and timestamps, and a .dat file of samples), plus SER logs for the same period.
- Read the configuration. From the .cfg file: channel names, units, primary/secondary scaling (CT and PT ratios), sample rate and the time stamp of the first sample, in UTC.
- Get plant real power. Use the recorded MW channel at the point that represents the whole plant (typically the POI or the high side of the main power transformer). If there isn't one, calculate three-phase real power from the voltage and current channels.
- Use gross nameplate. The 10% test is against the plant's gross nameplate rating, not output at the time. Take it from your asset record and keep it with the screening results.
- Slide a 4-second window. Across the full record, find the largest drop in real power inside any 4-second span. A slow 40 MW ramp over a minute doesn't qualify; a 25 MW drop in 2 seconds at a 150 MW plant does. See worked examples.
- Check for a complete loss. Output falling to zero qualifies regardless of size.
- Test the exclusions. Irradiance or wind data for the same seconds; dispatch, AGC or ramp logs; breaker and SER records showing a configuration disconnect; or a PRC-004 misoperation record.
- Log every result. Record file, time window, drop in MW and %, nameplate used, verdict and, for exclusions, the supporting record.
- Start the clocks. A qualifying event starts the 90-day R2 analysis; a needed correction starts the 60-day R3 Corrective Action Plan clock.
The sliding-window method in step 5 is our practice and the safest reading of R1; the standard's text governs.
Common screening mistakes
- Screening SCADA averages instead of high-resolution records, which hides fast drops.
- Using output at the time instead of gross nameplate for the 10% test.
- Measuring at one feeder or inverter group and treating it as the whole plant.
- Time stamps not in UTC, so exclusion records don't line up with the event.
- Keeping only the events, not the records that were screened and cleared.
Where data phleet fits
data phleet runs these steps on every COMTRADE record as it arrives: it reads the .cfg and .dat files, applies the R1 thresholds against gross nameplate from your asset record, tests exclusions against met-station, dispatch and SER data, logs every result and starts the R2 and R3 clocks for anything that qualifies. Your engineers do the root-cause analysis. You can see it run on a simulated plant in the booth demo.
Related questions
Can we screen PRC-030-1 events with SCADA data instead of COMTRADE?
Not reliably. R1 looks for a change within a 4-second period, and one-minute or hourly SCADA averages can hide a qualifying drop. Use the high-resolution records your PRC-028-1 recorders produce; SCADA is useful as context and for exclusions such as dispatch.
Do we have to keep screening results for records that didn't qualify?
Our recommendation is yes. M1 expects evidence that the detection process exists and runs. A log showing every record screened, with the result and the reason for any exclusion, is the simplest proof.
What if the record has no real power channel?
Compute real power at the point of measurement from the voltage and current channels (three-phase, with the correct CT and PT ratios from the .cfg file), then check that the measurement point represents the whole plant's output. If it doesn't, combine the records that do.
Which COMTRADE versions does data phleet read?
data phleet reads IEEE C37.111 COMTRADE records (.cfg and .dat, with .hdr where present, and the 2013 single-file .cff), along with SER logs and met-station data used for exclusions. See file formats.
Send us a month of records.
We'll screen them against R1 live and show you every qualifying event, every exclusion and the log behind it.